Monday, November 15, 2010

Submission of Assignment 1

ABSTRACT
The purpose of this assignment is to study several identified buildings taken around 2006 in Klang Valley appeared to have physical damage which is believe was struck by lightning. Preliminary found that some of the buildings were installed by lightning protection system but still being struck by lightning especially at the sharp edge while some were not protected and exposed to the strike. A grounding measurement was taken using one rod method and the result was analyzed. It found that not installing lightning protection, LPS installed not adhere to the standard and wrongly place the air terminal had increase a risk of the building being struck by lightning.

INTRODUCTION
Lightning is a natural phenomenon that happen due to electrical discharge between cloud to cloud (inter cloud and intra cloud) and cloud to ground (CG) generated by Cumulonimbus cloud. However in most cases, we are much interested with cloud to ground discharges because it can cause a physical damage to a structure, electrical damage to equipment as well as a threat to human safety. The discharge begins with stepped leader and it’s completed with return stroke (streamer). For multiple strokes it leads by dart leader as shown in Figure 1. The discharge was identified as negative flash (CG-) if a negative charges flow from the cloud to the ground and positive flash (CG+) if a positive charges flow from cloud to the ground.

Figure 1





There are several parameters related to lightning, for instance lightning ground flash density, thunderstorm day, isokeraunic, lightning stokes current and probability. Lightning ground flash density, Ng can be defined as the number of cloud-to-ground flashes in km-2 per year-1. Thunderstorm day, TD is also called keraunic level and defined as a local calendar day during which thunder is heard at least once at a given station while isokeraunic level map is a map of thunderstorm days in a year. The lightning ground flash density Ng is an important meteorological data that is used in calculating the risk of lightning strikes to a structure or system. The Ng used to be calculated from the annual thunderstorm days TD. A more accurate method of determining the Ng is by the use of a lightning detection system (LDS).
Malaysia is situated in a very active region of thunderstorm activity. Figure 2 shows a keraunic level map for Peninsular Malaysia. For further understanding about lightning behavior at that location, normally a study was done in term of temporal analysis and spatial analysis.

Figure 2











In 1995, Peninsular Malaysia was estimated to have average ground flash density (Ng) 4.40 flashes/sq.km/year[1]. 4% of the flashes were positive flash as shown in Table 1

Table 1



METHODS OF LIGHTNING PROTECTION
Lightning protection is essential for the protection of humans, structures, contents within structures, transmission lines and electrical equipment from thermal, mechanical and electrical effects caused by lightning discharges. Lightning cannot be prevented, but it can with some success be intercepted, and its current can be conducted to a grounding system without side flashes where it is harmlessly dissipated.
The methods of lightning protection are well described using the zone of protection concepts for a structure. The zone of protection is the space within the volume to be protected and where the lightning protection air termination is located. Air termination can have different forms such as:

• Rods;
• Stretched wires; and
• Meshed conductors.
In order to place the air termination in a proper position on the building to be protected, the following methods can be used:

• The protective angle method.
• The rolling sphere method.
• The mesh method.
• Faraday cage method.

Protective Angle Method
The structure to be protected lies within an imaginary cone ABC with the highest point of the structure providing protection as shown in Figure 3. Table 2 provides the recommended values for the cone angle, α (in degrees).

Table 2





The protection angle method is suitable for simple buildings. If the height is larger than the rolling sphere radius, R, the protection angle method cannot be used.

The zone of protection offered by an air termination system is considered to be 45º for heights up to 20m. Above this height, the zone of protection is determined by the rolling sphere method.

Figure 3








Rolling Sphere Method
The rolling sphere method is used when we are dealing with complex structures. When the use of the protective angle method is excluded, the rolling sphere method is used to identify the protected volume of the structure.

This involves rolling an imaginary sphere of radius given in Table 3 over a structure. The areas touched by the sphere are deemed to require protection as shown in Figure 4. On tall structures, this can obviously include the sides of the building.

Table 3




Figure 4




If two parallel horizontal LPS air terminations are placed above the horizontal reference plane as shown in Figure 5, the penetration distance p of the rolling sphere below the level of the air terminations is calculated as follows:

Equation 1




p is the penetration distance of rolling sphere, R is the radius of rolling sphere and d is the distance separating two air terminations.

Figure 5





1 – Two air termination, 2- horizontal reference plane, 3- whole protected area, ht- physical height of the air termination above the reference plane. This height is given in Table 1.

The Mesh Method
The mesh method is suitable for protecting flat surfaces. BS 6651 recommends that on high risk structures such as explosive factories and thatched roofs, no part of the roof should be more than 2.5m from an air termination conductor. This is generally achieved by applying a 5m x 10m mesh to the roof.

However, for most structures, a mesh of 10m x 20m is considered sufficient, giving a maximum distance from any part of the roof to the nearest conductor of 5m. All metal structures on the roof would be interconnected using this mesh.

The recommended sizes for the mesh according to their protection level are listed in Table 4.

Table 4


Faraday Cage Method
Electromagnetic radiation is associated with lightning and can cause damages to the sophisticated electronics in a building. Prevention of such intrusion of undesired electromagnetic impulses through both radiation and conduction is termed Electro Magnetic Compatibility (EMC). “Faraday Cage” is the usual method of radiation prevention, in which building will be screened with the conductive materials so that the structure behaves like cage as shown in Figure 6. The interior of a completely enclosed metal shell is free from the effects of any external changes of electric field. This method of protection is provided to the part of the building where sophisticated electronics are installed (such as computer rooms, medical theatres and scanning rooms, control chambers of power plants, airports, military bases, and communication bases etc.).

Figure 6


LIGHTNING PROTECTION - ROD
The standard LPS which are comply with the national or international technical standard that has been scientifically proven to provide safety to users. The standard LPS component consists of conventional air terminal, down conductor and earth terminal [2].
The main component of standard LPS is conventional air terminal (Franklin rod) which has been invented by Benjamin Franklin in 18th century. After more than 350 years, the Franklin rod is still in use throughout the whole world and has been scientifically validated by two major studies group which was AGU and Federal Interagency Lightning Protection User Group. It is a passive device and serves as a sacrificial device when the lightning strikes it rather than building structure. It can be installed at various locations on the rooftop that are likely strike by lightning. Therefore, the building is protected by direct lightning strike [2]. Figure 7 shown Conventional lightning rod installed on the building rooftop.


Figure 7




The ESE Air Terminal is a device which creates an upward propagating streamer faster than conventional lightning rod (Franklin rod). When downward leader from the thunderstorm is approaching to ground surface, ESE Air Terminal has short initiation time in microseconds of creates an upward streamer compare to conventional lightning rod. There are different types of ESE Air Terminal on the market today. Each type of ESE Air Terminal has a different protective radius stated by its manufacture [3] [4]. Figure 8 below shown ESE Air Terminal lightning rod installed on the building rooftop.

Figure 8





FACTORS AFFECTING SOIL RESISTIVITY
Factors that affecting soil resistivity may be summarized as below:
a) Type of earth (eg, clay, loam, sandstone, granite).
b) Stratification; layers of different types of soil (eg, loam backfill on a clay base).
c) Moisture content; resistivity may fall rapidly as the moisture content is increased, however after a value of about 20% the rate of decrease is much less. Soil with content greater than 40% does not occur very often.
d) Temperature; above freezing point, the effect on earth resistivity is practically negligible
e) Chemical composition and concentration of dissolved salt.
f) Presence of metal and concrete pipes, tanks, large slabs, cable ducts, rail tracks, metal pipes and fences
g) Topography; rugged topography has a similar effect on resistivity measurement as local surface resistivity variation caused by weathering and moisture




SOIL RESISTIVITY TEST METHOD

Wenner Method

Figure 9




In the Wenner method, all four electrodes are moved for each test with the spacing between each adjacent pair remaining the same. The Wenner array is the least efficient from an operational perspective. It requires the longest cable layout, largest electrode spreads and for large spacings one person per electrode is necessary to complete the survey in a reasonable time. Also, because all four electrodes are moved after each reading the Wenner Array is most susceptible to lateral variation effects.
However the Wenner array is the most efficient in terms of the ratio of received voltage per unit of transmitted current. Where unfavorable conditions such as very dry or frozen soil exist, considerable time may be spent trying to improve the contact resistance between the electrode and the soil.

Equation 2



Where ρaw = apparent resistivity (Ω) I = injected current (Amps)
a = probe spacing (m) R = measured resistance (Ω)
Δv = voltage measured (volts)

Schlumberger Method

Most widely used in electrical prospecting. Two current electrodes may be placed a large distance apart and the potential electrodes moved along the middle third of the line.
Economy of manpower is gained with the Schlumberger array since the outer electrodes are moved four or five times for each move of the inner electrodes. The reduction in the number of electrode moves also reduces the effect of lateral variation on test results.
Considerable time saving can be achieved by using the reciprocity theorem with the Schlumberger array when contact resistance is a problem. Since contact resistance normally affects the current electrodes more than the potential electrodes, the inner fixed pair may be used as the current electrodes, a configuration called the ‘Inverse Schlumberger Array’. Use of the inverse Schlumberger array increases personal safety when a large current is injected. Heavier current cables may be needed if the current is of large magnitude. The inverse Schlumberger reduces the heavier cable lengths and time spent moving electrodes. The minimum spacing accessible is in the order of 10 m (for a 0.5m inner spacing), thereby, necessitating the use of the Wenner configuration for smaller spacings.
Lower voltage readings are obtained when using Schlumberger arrays. This may be a critical problem where the depth required to be tested is beyond the capability of the test equipment or the voltage readings are too small to be considered.


Figure 10




With the Schlumberger array the potential electrodes remain stationary while the current electrodes are moved for a series of measurements. In each method the depth penetration of the electrodes is less than 5% of the separation to ensure that the approximation of point sources, required by the simplified formulae, remains valid.

Schlumberger array

Equation 3





Where ρas = apparent resistivity (Ωm)
l = distance from centre line to inner probes (m)
L = distance from centre line to outer probes (m)
R = measured resistance (Ω)


One rod method
This is the simplest method compared to Wenner and Schlumberger method above. The test is based on measuring the resistance of a single rod that is driven into the ground for a known depth. The resistance measurement and rod dimensions are then used to calculate the average soil resistivity required to produce the measured resistance.
The earth resistance of a rod will usually reduce as its driven depth is increased. The resistance of a rod should never increase with driven depth. It is the rate at which the resistance decreases with depth that allows the soil structure and layer resistivity to be determined. Soil structure where the deeper layer has a lower resistivity than the upper, will produce sudden changes in the gradient of the rod’s resistance curve. Where the top layer has a lower resistivity than the lower layers then the structure is more difficult to determine, as the test current will tend to continue to flow in the top, lower resistivity layer. The resulting low current density in the higher resistivity layer has little influence on the measured of the rod. Where a very high resistivity stratum is penetrated, the rod resistance may remain virtually constant with increasing depth. If a further lower resistivity layer is penetrated beneath this, then the rod resistance will again begin to decrease with increasing depth.


CASE STUDY 1: RISDA building, Jalan Ampang

The building was struck by lightning at the corner roof structure, where the ESE air terminal installed about 30metres away at the highest location from the corner roof structure. This was primarily due to air terminal is not effective in providing sufficient protection on all the roof structure.

Figure 11




From our observation recently, the defect at the building had been rectified by RISDA management. To improve the lightning protection, the management had increased the number of lightning conductor at strategic point on top of the building to enlarge the protection radius in case if the lighting strikes to the building. A lightning conductor mounted on top of a building and electrically connected to the ground through a wire, to protect the building from damage due to lightning strikes. In case if the lightning strikes to the building it will preferentially strike the rod and be conducted to ground through the wire, instead of passing through the building.

Figure 12






Figure 13



To measure soil resistivity of the RISDA building, we had used driven rod method or also called the three probe method or three pin method. The purpose of resistivity testing is to obtain a set of measurements which may be interpreted to yield an equivalent model for the electrical performance of the earth, as seen by the particular earthing system.
From the investigation of soil resistivity of the RISDA area it shows that in many locations, the types of soil are sand and it can be quite homogenous. A set of readings taken with various probe spacing gives a set of resistivity (see Appendix 1). The range of soil resistivity is between 371 Ωm – 445 Ωm. The factors chiefly affecting soil resistivity is type of soil, climate, seasonal conditions and others factors. From all of these factors, there is a large variation of soil resistivity between different soil types and moisture contents.
In addition, the weather was around 32 ºC measurement reading taken and it was contributed to a low resistance value since the condition of the soil was dry with low percentage of moisture content.






CASE STUDY 2: The Mall, Kuala Lumpur

The Mall is located at Jalan Putra, Kuala Lumpur. The Legend Hotel is located beside The Mall. Currently, the lightning struck below the edge of the roof still visible from the distance can be shown in Figure 12 and haven’t repaired it. So, our group member will use KYORITSU (Model 4102) to measure the grounding resistivity on 25-9-2010 Saturday. After measurement has been done, we record our results on the earth resistivity measurement report.

Figure14



Figure15




From the report that we recorded (see Appendix 2), we found that the grounding resistivity is relativity small. It means that The Mall of the grounding resistivity is in good condition. Since The Mall did not install with any lightning rod at their rooftop, The Legend Hotel was installed with ESE Air Terminal on their rooftop which was higher height than The Mall can be shown in Figure 13. Although The Legend Hotel was installed ESE Air Terminal, but the lightning struck below the edge of the roof at The Mall and The Legend Hotel. The reason is because The Legend Hotel installed with non-standard LPS. The non-standard LPS which are did not comply with the national or international technical standard that has been scientifically proven to provide safety to users. Besides that, the non-standard LPS are usually easier and cheaper to install compared to standard LPS [2]. So, the consultant of the building installed the ESE Air terminal at The Legend Hotel did not follow according to the MS IEC 61024-1-1:2001 Malaysia Standard.

CASE STUDY 3: General Hospital, Kuala Lumpur

In set picture taken in 2006 shown that the edge of the building was struck by lightning that cause a physical damage to the building as shown in Figure 14. From our observation in a visit recently to the building found that the building was left unoccupied for quite some time, this could justify the damage remains unrepaired. It was understand that the building will undergo major renovation to improve services.

Figure 16



Figure 17




Figure 18




Figure 18, shown that no lightning protection was installed on top of that old building. Alternatively, water piping was used to measure soil resistivity at that area and the result shows it has a good soil resistivity (see appendix 3).




CASE STUDY 4: SuCasa Service Apartment, Kuala Lumpur

SuCasa Service Apartment is located at Jalan Ampang, Kuala Lumpur. The soil resistivity test was carried out on October 9, 2010 using one-rod method. The lightning protection system installed at the building is a conventional franklin rod type. We found that this building is exposed to the lightning strike because of the earth resistivity is quite high (see Appendix 4). This may be regarding to the soil type at that area (sand/gravel).


Figure 19






CONCLUSION
As a summary to the case study:
1) Case Study 1: Risda.
• Lightning protection was installed but not according to the standard, hence insufficient protection to the building.
• An improvement was done by increasing the number of air terminals at a strategic location.

2) Case Study 2: The Mall.
• Grounding measurement shows a relatively small resistivity and good for conductivity.
• No lightning protection system installed has exposed the building to lightning strike.

3) Case Study 3: General Hospital.
• Grounding measurement shows a relatively small resistivity and good for conductivity.
• No lightning protection system installed has exposed the building to lightning strike.

4) Case Study 4: Sucasa Service Apartment.
• Lightning protection was installed but not according to the standard, hence insufficient protection to the building.
• High grounding resistivity at that area also contribute to the failure of lightning protection.

Based on the case study, it can be concluded adhering to the standard is important when installing lightning protection to ensure the building is fully protected. All figures above shown that the lightning will strike at the edge due to charge density is high at a sharp edge. Hence by placing the air terminal at a strategic location also can reduce a risk of being struck by lightning.

REFERENCES
[1] The Study of Lightning Ground Flash Phenomena in Peninsular Malaysia, MD Ahsanul Alam, 1996.
[2] Conventional and Un-conventional Lightning Air Terminal: An Overview, Hartono Zainal Abidin & Robiah Ibrahim, 8th January 2004.
[3] Evaluation of Early Streamer Emission Air Terminal, Scott D. Mclvor, Roy B. Carpenter, Jr., Mark M. Drabkin.
[4] Eritech System 1000: ESE Lightning Protection Products.


APPENDIX
Appendix 1: measurement taken at RISDA
Appendix 2: measurement taken at The Mall
Appendix 3: measurement taken at HKL
Appendix 4: measurement taken at Sucasa Service Apartment.

GREAT EFFORT: MMSC Consultancy Team Member

MMSC member


Thursday, August 12, 2010

Case Study

Case 1: The Mall, Kuala Lumpur

Building struck by lightning below the edge of The Mall, Kuala Lumpur. No conventional or unconventional lightning protection system available close to the stricken. But, The Mall is actually attached to Legend Hotel where there is ESE air terminal installed on top of the building as shown in the Plate no: 1.



Plate No: 1: Lightning struck below the edge of the roof at The Mall, Kuala Lumpur where that area is not protected by lightning protection system.



Case 2: SuCasa Service Apartment, Jalan Ampang, Kuala Lumpur

Lightning struck at a roof structure of the building, and there are 2 locations of lightning strike points adjacent to each other.




Plate No: 2 The sharp edges of the building experienced damages



Case 3: Grandeur Tower, Ampang

Building in the same locations badly damaged by lightning struck (refer to Plate No3 ). Notice the same location of the lightning struck at the corner of the roof and the pointed roof structure, showing poor lightning protection system installed or probably no lightning protection installed on top of the roof. One is unable to locate any conventional or unconventional lightning protection system. Almost 70% of the sharp edges of this building being struck by lightning. From the condition of the damages there is a possibility of multiple struck were repeatedly occurred.


(a)


(b)

Plate No 3 :The sharp edge of the building experienced lightning related damages i.e lightning struck at the corner section of a roof at Grandeur Tower, Ampang for case (a) and (b).


Case 4: Bangunan Risda, Jalan Ampang

Building struck by lightning at the corner roof structure, the ESE air terminal installed about 30metres away at the highest location from the corner roof structure. Air terminal is not effective in providing sufficient protection on all the roof structure.



Plate No 4: Lightning struck at the corner section of a roof at Bangunan Risda, Kuala Lumpur. ESE air terminal installed at the highest point of the building, but unable to protect the edge of the building


Case 5: Bukit Rawang Jaya Apartment


Plate No 5: Lightning struck at the gable of the roof at Bukit Rawang Jaya apartment notice Franklin rod at the edge of the roof.



Case 6: Low-cost Apartment in Kuantan, Pahang
Damaged at the top of the building and far from the protection rod.


Plate No.6: Lightning struck at the gable of the roof at a apartment in Kuantan


Case 7: Lafarge Building, Kuala Lumpur.


Lightning related Damaged at the edge of the building but surprisingly that spot is very near to the protection rod.



Plate No.7: Lightning struck at the sharp edge of the building top overlooking it is the Franklin Lightning Rod



Case 8 Kuala Lumpur General Hospital



Physical damage at the edge of the building leaving a chisel like edges


Plate No. 8: Lightning struck at the roof edge of Kuala Lumpur General Hospital


Case 9: Flextronics Building, Johore Bahru



Plate No.9: Lightning struck at the parapet wall of Flextronics.



The physical damage is quite serious where a big chunk of the building wall has fall off the building.



Case 10:Shop Houses, Nilai, Negeri Sembilan.

Plate No.10: Lightning struck at the concrete slap of the building top

Case 11: Multi-storey apartment, Kuantan, Pahang


Plate No. 11: The roof tiles were flown away and damaged due to lightning strike


Case 12: Building in Kuala Lumpur



(a)


(b)


Plate 12: a) A close-up new of the building parapet wall damaged due to lightning strike b) vertical closed-up view of lighning related damad

Types of Grounding

1. Ungrounded.
Electrical power systems that are operated with no intentional connection to earth ground are described as ungrounded. Although these systems were standard in the '40s and '50s, they're still in use today. The main advantage of this type of grounding system is that it offers a low value of current flow and reliability during a fault. Unfortunately, this type of system also offers some big disadvantages. One major disadvantage to an ungrounded system is in the difficulty in locating a line-to-ground fault. Finding the fault is a time consuming process. For that reason, it's often done on the weekends so a company doesn't have to shut down its normal production processes. In addition, the fault must be located and repaired quickly because if a second fault occurs, the fault acts like a phase-to-phase fault extending the repair process.

Advantages


•Offers a low value of current flow for line-to-line ground fault (5A or less).
•Presents no flash hazard to personnel for accidental line-to-ground fault.
•Assures continued operation of processes on the first occurrence of a line-to-ground fault.
•Low probability of line-to-ground arcing fault escalating to phase-to-phase or 3-phase fault.
Disadvantages


•Difficult to locate line-to-ground fault.
•Doesn't control transient overvoltages.
•Cost of system maintenance is higher due to labor involved in locating ground faults.
•A second ground fault on another phase will result in a phase-to-phase short circuit.
2. Solidly grounded.
This type of grounding system is most commonly used in industrial and commercial power systems, where grounding conductors are connected to earth ground with no intentional added impedance in the circuit. A main secondary circuit breaker is a vital component required in this system, although it has no bearing in other grounding systems. This component is large in size because it has to carry the full load current of the transformer. Back-up generators are frequently used in this type of grounding system in case a fault shuts down a production process. When this happens, the generators become solidly grounded. However, it's important to note that the generators aren't designed for the larger short circuit current associated with solidly grounded systems.

A solidly grounded system has high values of current ranging between 10kA and 20kA. This current flows through grounding wires, building steel, conduit, and water pipes, which can cause major damage to equipment and shut down production processes. When a line-to-ground fault occurs, arcing can create flashes-generally in the terminating box. In this enclosed area, water is turned to steam, causing the terminating box. To locate the fault, all you need to do is follow the smoke.

Advantages


•Good control of transient overvoltage from neutral to ground.
•Allows user to easily locate faults.
•Can supply line-neutral loads.
Disadvantages


•Poses severe arc flash hazards.
•Requires the purchase and installation of an expensive main breaker.
•Unplanned interruption of production process.
•Potential for severe equipment damage during a fault.
•High values of fault current.
•Likely escalation of single-phase fault to 3-phase fault.
•Creates problems on the primary system.

3. High-resistance grounding.
High-resistance grounding (HRG) systems are commonly used in plants and mills where continued operation of processes is paramount in the event of a fault. High-resistance grounding is normally accomplished by connecting the high side of a single-phase distribution transformer between the system neutral and ground, and connecting a resistor across the low-voltage secondary to provide the desired lower value of high side ground current. With an HRG system, service is maintained even during a ground fault condition. If a fault does occur, alarm indications and lights help the user quickly locate and correct the problem or allow for an orderly shutdown of the process. An HRG system limits ground fault current to between 1A and 10A.

Advantages


•Limits the ground fault current to a low level.
•Reduces electric shock hazards.
•Controls transient overvoltages.
•Reduces the mechanical stresses in circuits and equipment.
•Maintains continuity of service.
•Reduces the line voltage drop caused by the occurrence and clearing of a ground fault.
Disadvantages


•High frequencies can appear as nuisance alarms.
•Ground fault may be left on system for an extended period of time.

Introduction: Assignment 1

Background:
MMSC Consultancy was established to study based on the case study given, why grounding system failed to provide protection and had caused a physical damaged to commercial and residential building. This project is under supervision of Prof. Hussien Ahmad, director of IVAT from UTM Malaysia.


MMSC Consultancy member's:
1. Mohd Hayriel Salim (TL)
2. Chong Kiat Shiu
3. Siti Aishah Bakar
4. Mariam Mat Saad
All members are currently pursuing a Master in Electrical Engineering.

Objective of the assignment:
1. To investigate why Franklin Rod failed to capture the lightning.
2. Explanation on edge surface is more prone to lightning strike.
3. Based on the study, to provide a recommendation to avoid the repeated fault.

Strategies:
1. To do measurement on the grounding system.
2. To check soil resistivity at the location.
3. To indentify class of protection installed on the building using angle of protection and rolling sphere.
4. To investigate the root cause that reduces the effectiveness of the Franklin Rod. i.e: copper degradation and cable theft.


Delegation:
1. Hayriel – Logistic
2. Chong – Equipment
3. Aishah – Documentation
4. Mariam – Theoritial